Accuracy | Cx | ± (reading) × 1%+1pF) |
tg δ | ± (reading) × 1%+0.00040) | |
Anti interference index | frequency conversion anti-interference, which can still achieve the above accuracy under 200% interference | |
Capacitance range | Internally applied high pressure | 3pF~60000pF/10kV 60pF~1 μ F/0.5kV |
Externally applied high voltage | 3pF~1.5 μ F/10kV 60pF~30 μ F/0.5kV | |
resolving power | Up to 0.001pf, 4 significant digits | |
tg δ Range | Unlimited, resolution 0.001%, automatic identification of capacitance, inductance and resistance. | |
Test current range | 10 μ A~5A | |
Internally applied high pressure | Set voltage range | 0.5 ~ 10KV |
Maximum output current | 200mA | |
Voltage rise and fall mode | the voltage is set at will. For example, 5123v. | |
Test frequency | 40-70HZ, single frequency set at will. For example, 48.7hz | |
Automatic double frequency conversion from 50 ± 0.1Hz to 50 ± 10Hz can be set at will. | ||
Automatic double frequency conversion from 60 ± 0.1Hz to 60 ± 10Hz can be set at will. | ||
Frequency accurac | ±0.01Hz | |
Externally applied high voltage | The maximum test current during positive connection is 5a, power frequency or frequency conversion is 40-70HZ | |
The maximum test current during reverse wiring is 10kV / 5A, power frequency or frequency conversion is 40-70HZ | ||
CVT self excitation low voltage output | output voltage 3 ~ 50V, output current 3 ~ 30A | |
Measurement time | About 40s, related to the measurement method | |
Input power supply | 180V ~ 270vac, 50Hz ± 1%, mains power or generator power supply | |
Computer interface | standard RS232 interface, USB flash disk socket (automatic USB flash disk data storage). | |
Printer | micro thermal printer | |
ambient temperature | – 10 ℃ ~ 50 ℃ | |
relative humidity | < 90% | |
Overall dimension | 460 × 360× 350mm | |
instrument weight | 28KG | |